100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
Page 134
4.3.13 COUNTERS (Cont.)
COUNTER MODBUS ADDRESSING
The table below gives addresses for counter 1 confi guration data. Generally: Counter N parameter ad-
dress = counter 1 parameter a 162 (N-1) (decimal). For full details of the Modbus implementa-
tion, see
section 8
.
COUNTER CONFIGURATION DATA
COUNTER 1
Note: A/B Switching:
B values are not accessible via modbus
for this software version. Span, Zone,
Colour etc. are therefore all setting A
Notes:
1. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
2. If more than 100 Maths channels are confi gured in ‘
Virtual channels
’, then the extra channels
occupy totaliser address space such that maths channel 101 occupies totaliser 1 address and so
on. Totaliser 1 value is to be found at the fi rst address after the fi nal maths channel. Thus, if there
are, for example, 105 maths channels, then Totaliser 1 is found where Totaliser 6 would normally
be. This in turn affects counter addressing as counter addresses immediately follow totaliser ad-
dresses, and in the above example, Counter 1 value would be found at counter 6 address.
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Span high
Upper span value (display full scale)
Scaled
Read only
8EDD (36573)
1
Span low
Lower span value (display ‘zero’)
Scaled
Read only
8EDE (36574)
1
Zone high
Zone high value (two decimal places)
Scaled
Read only
8EDF (36575)
1
Zone low
Zone low value (two decimal places)
Scaled
Read only
8EE0 (36576)
1
PV type
Input type
Enum
Read only
8EE1 (36577)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Decimal places
Number of decimal places (0 to 9)
Uint16
Read only
8EE2 (36578)
1
(used by all scaled parameters except where stated)
Colour
Channel colour (0 to 55) (See
Annex B
for defi nitions)
Enum
Read only
8EE3 (36579)
1
Units
Units string (up to fi ve characters)
String_5
Read only
8EE4 (36580)
3
Spare
8EE7
(36583)
2
Open string
Open Digital Input string (up to eight characters)
String_8
Read only
8EE9 (36585)
4
Spare
8EED
(36589)
4
Close string
Closed Digital Input string (up to eight characters)
String_8
Read only
8EF1(36593)
4
Spare
8EF5
(36597)
4
Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only
8EF9 (36601)
10
Spare
8F03
(36611)
10
No of alarms
Number of alarms on this channel
Uint16
Read only
8F0D (36621)
1
PV format
Enum
Read only
8F0E (36622)
1
0 = Numeric
1 = Digital strings
Spare
8F0F
(36623)
60
Alarm 1 enable
Alarm 1 enable
Enum
Read only
8F4B (36683)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Alarm 1 type
Alarm 1 type
Enum
Read only
8F4C (36684)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Alarm 1 setpoint
Trigger setpoint (see note)
Scaled
Read/Write 8F4D (36685)
1
Spare
8F4E
(36686)
10
Alarm 2 enable
Alarm 2 enable (As alarm 1 enable above)
Enum
Read only
8F58 (36696)
1
Alarm 2 type
Alarm 2 type (As alarm 1 type above)
Enum
Read only
8F59 (36697)
1
Alarm 2 setpoint
Trigger setpoint (see note)
Scaled
Read/Write 8F5A (36698)
1
Spare
8F5B
(36699)
10
Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only
8F65 (36709)
1
Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only
8F66 (36710)
1
Alarm 3 setpoint
Trigger setpoint (see note)
Scaled
Read/Write 8F67 (36711)
1
Spare
8F68
(36712)
10
Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only
8F72 (36722)
1
Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only
8F73 (36723)
1
Alarm 4 setpoint
Trigger setpoint (see note)
Scaled
Read/Write 8F74 (36724)
1
Spare
8F75
(36725)
10