100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
Page 192
HA029324
Issue 11 Oct 14
4.4.2 Management (option)
Note: Where users are controlled by a domain on the recorder, Security Manager will not manage
or reconcile disabled accounts, password changes or password expiry on these recorders.
This menu selection appears only if the Audit Trail option, 21CFR11 option and/or Security Management
option is fi tted. Which confi guration fi elds appear depends on the option(s) fi tted. Figure 4.4.2a, below,
shows the confi guration menus for the various combinations.
The 21CFR11 option allows the recorder to be set up so that all changes to confi guration (with the ex-
ceptions listed below) are added to the history fi les and also allows certain constraints to be placed on
the recorder passwords. Once these items of confi guration are set up, they apply to all groups. Figure
4.4.2a, below, shows the confi guration menu.
Record Logins
with unapplied changes
Minimum Password Length
Enable Audit Trail
Require Authorization
Apply
Discard
Login Timeout
Password Attempts
Passwords Expire
Require Signing
1
3 times
30
3
Ignore timeout
Days
Minutes
This field appearsonly if Login
timeout is non-zero
Password Change on Expiry
Centralised Security
This field appears only if
'Require Signing' is enabled
Login By User List
This item appears only if the Securiy Management
option is fitted. If enabled, all other security fields can
be edited only via Security Management software.
This item appears only if one or more of Security
Management, Audit trail or 21CFR11 options is
fitted.
Centralised Security
Apply
Discard
Login By user List
Record Logins
Centralised Security
Enable Audit Trail
This item appears only if the
Security Management option
is fitted.
Login By user List
Apply
Discard
2 Security Manager
Audit Trail + Security Manager
Security Manager only
Figure 4.4.2a Management menu structure
CHANGES NOT RECORDED
Changes to confi guration made via MODBUS/TCP are not recorded. It is up to the user to write the iden-
tity, time/date, reason for change etc. as text messages, which when sent via MODBUS/TCP, become part
of the relevant history fi le.
CONFIGURABLE PARAMETERS
Notes:
1. Unless otherwise indicated, the following parameters appear only if the Auditor 21CFR11 op-
tion is fi tted.
2. If Centralised Security is enabled, none of the other paramete rs in this menu can be edited at
the recorder. Changes can be made only using Security Management software.