100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
Page 178
HA029324
Issue 11 Oct 14
4.3.21 ETHERNET/IP OPTION (Cont.)
DEFAULT TABLE KEY
Clicking on this key causes the relevant table to be populated with a default set of parameters.
For input tables, these parameters are: Channel.1.pv to Channel.100.pv followed by Math.1.pv to Math.100.pv.
The output table parameters are: Channel.1.pv to Channel.100.pv followed by Math.1.pv to Math.100.pv.
SHOW ERRORS KEY
Clicking on this key causes the parameter addresses to appear after the parameter names in the input
and output tables. If a syntax or other error has been made in loading the input table, a description of
the error type appears in this view (see ‘
ERROR MESSAGES
’, above).
OUTPUT TABLE PARAMETER MODBUS ADDRESSES
In all cases, the addresses for the output parameters can be viewed by operating the ‘Show errors’ key.
The addresses for channels 1 to 75 and maths 1 to 100 can be found as described in
Section 8.4.3
(Chan-
nel Runtime data), and
section 4.3.11
(Maths channel Run-time data). Addresses for channels 76 to 100,
are given below:
Channel.76.pv
Channel 76 process value
Scaled
Read only
FCBF (64703)
1
Channel.77.pv
Channel 77 process value
Scaled
Read only
FCC2 (64706)
1
Channel.78.pv
Channel 78 process value
Scaled
Read only
FCC5 (64709)
1
Channel.79.pv
Channel 79 process value
Scaled
Read only
FCC8 (64712)
1
Channel.80.pv
Channel 80 process value
Scaled
Read only
FCCB (64715)
1
Channel.81.pv
Channel 81 process value
Scaled
Read only
FCCE (64718)
1
Channel.82.pv
Channel 82 process value
Scaled
Read only
FCD1 (64721)
1
Channel.83.pv
Channel 63 process value
Scaled
Read only
FCD4 (64724)
1
Channel.84.pv
Channel 64 process value
Scaled
Read only
FCD7 (64727)
1
Channel.85.pv
Channel 65 process value
Scaled
Read only
FCDA (64730)
1
Channel.86.pv
Channel 66 process value
Scaled
Read only
FCDD (64733)
1
Channel.87.pv
Channel 67 process value
Scaled
Read only
FCE0 (64736)
1
Channel.88.pv
Channel 68 process value
Scaled
Read only
FCE3 (64739)
1
Channel.89.pv
Channel 69 process value
Scaled
Read only
FCE6 (64742)
1
Channel.90.pv
Channel 70 process value
Scaled
Read only
FCE9 (64745)
1
Channel.91.pv
Channel 71 process value
Scaled
Read only
FCEC (64748)
1
Channel.92.pv
Channel 72 process value
Scaled
Read only
FCEF (64751)
1
Channel.93.pv
Channel 73 process value
Scaled
Read only
FCF2 (64754)
1
Channel.94.pv
Channel 74 process value
Scaled
Read only
FCF5 (64757)
1
Channel.95.pv
Channel 75 process value
Scaled
Read only
FCF8 (64760)
1
Channel.96.pv
Channel 76 process value
Scaled
Read only
FCFB (64763)
1
Channel.97.pv
Channel 77 process value
Scaled
Read only
FCFE (64766)
1
Channel.98.pv
Channel 78 process value
Scaled
Read only
FD01 (64769)
1
Channel.99.pv
Channel 79 process value
Scaled
Read only
FD04 (64772)
1
Channel.100.pv
Channel 80 process value
Scaled
Read only
FD07 (64775)
1
Table 4.3.21 Parameter addresses for channels 76 to 100
CONFIGURING A PLC
The following instructions describe how to confi gure a PLC to communicate with a Paperless graphic
recorder. Although a specifi c PLC was used in generating these instructions, the detail should be general
enough to allow any other PLC to be used.
Parameter Description
Type
Access
Start
Addr.
Register
Name
Hex
(Dec)
Length
Summary of Contents for 6100