100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
User Guide
Page 326
9.5 REPORT EXAMPLE
This example shows how to con
fi
gure a report to be printed if any of channel 1 to channel 4 go into alarm. It
is assumed that the Serial comms link with the printer has been successfully established.
The report is to include the process values of channels 1 to 4 and the time and date.
Note: The example assumes that the channels being con
fi
gured are in their factory default state. Con-
fi
guration items not mentioned in the example (e.g. Scale Low) should be left at their default values.
9.5.1 Group Con
fi
guration
Refer to
section 4.3.2
, as necessary.
GROUP NUMBER 1
Descriptor = Colour mix.
Alarm message = Disable
Deselect all points except Channels 1 to 4.
9.5.2 Channel con
fi
guration
Refer to
section 4.3.3
as necessary
CHANNEL 1
Input Type = Test
Scale High =100
Units = %
Descriptor = Red
Alarm 1
Enable = Unlatched
Type = Absolute low
Threshold = 10
CHANNEL 2
As channel 1, except
Descriptor = Blue
CHANNEL 3
As channel 1, except
Descriptor = Green
CHANNEL 4
As channel 1, except
Waveform = Sine 4 minutes
Descriptor = Orange
Summary of Contents for 6100