FAP54 Programming
13
2 OPERATING MODES
The FAP54 control panel has two operating modes:
scanning phase
and
programming phase
.
When FAP54 is powered on, the scanning phase will be always started and maintained until the installer or the user
carries out an intervention.
2.1 SCANNING PHASE
In this operating mode the control panel monitors the devices scattered in the field and manages the following events:
alarm
general fault
field fault
maintenance
exclusion
events related to slave control panels (if the control panel is set as master)
generic events (not classified into any of the previous categories)
Normally, if there are not active events, the display on the control panel front side shows the following message:
The event indicator is shown when at least one event has occurred since the last time a level 2 password has been
inserted. If no event has occurred, a blinking asterisk will be displayed instead of the event indicator.
If the control panel has not been programmed yet, the display shows the message “
MONITORING NOT POSSIBLE
”.
If an event occurs, the display shows the event, along with the cumulative counters for each type of event on the right-
hand side.
Should more events occur, the display shows, in addition to the event counter increase, the first event occurred at the
top and the most recent alarm (if present) at the bottom.
The events are displayed according to the following priority:
Zones in alarms (ZA)
General faults (GF)
Field faults (FF)
Exclusion (EX)
Group of devices in alarm (GD)
Group of zones in alarm (GZ)
Maintenance (MN)
Events related to SLAVE control panels (SP)
Generic events (GE)
By using the keys
and
it is possible to change the type of event displayed (the > symbol on the right selects the
type of the event currently shown on the first two rows).
By using the keys
<
and
>
it is possible to go back and forth through the events of the selected type.
The selected event will be displayed at the top, while the most recent alarm event will be displayed at the bottom (if at
least one alarm is present) or nothing will be displayed.
Time
#
FIRE DETECTION SYSTEM
12/05/2021 11:50:42
FAP54-04
Date
Type of control panel
System name
Event indicator
Event cumulative
counters
ALM Z002 D00 C01 P015 SM A101 >ZA003
KITCHEN DETECTOR GF000
ALM Z110 D00 C01 P018 SM A101 FF000
CORRIDOR DETECTOR EX000
First event occurred
Last alarm occurred
Summary of Contents for FAP54
Page 151: ...FAP54 Programming 151 ...