FAP54 Programming
43
ZONE: XXX
ZONE: XXX
NAME: XXXXX
CIRCUIT: XX
ZONE: XXX
NAME: XXXXX
CIRCUIT: XX DEVICE:XX
ZONE: XXX
NAME: Name of the zone
CIRCUIT: XX DEVICE: XX TP.: YY
NAME: XXXXXXXXXX
ZONE: XXX
NAME: XXXXX
CIRCUIT: XX DEVICE: XX TP.: YY
CONFIRMED
3.2.2
Associate device to zone
Type in the number of the zone to be associated with the devices and then confirm with
OK
.
Now enter the coordinated (circuit number and device address) of the first device to be associated and confirm with
OK
:
The selected device will be displayed along with type and name.
Keys
are used to scroll the valid devices on the selected circuit.
To confirm a device selection press
OK
Key.
The confirmation message will be displayed:
By keeping
OK
pressed, the successive devices will be inserted in sequentially.
In theory, all the devices (not output modules) of the system can be associated simultaneously to the same zone.
Nevertheless,
it is good practice to associate no more than 32 devices per zone
(in order to verify the number of
devices currently associated to the zone, use the verification menu,
paragraph 3.2.6 Include/Exclude
),
otherwise the
system would not be compliant with the standard EN 54-2.
To delete the association between a device and a zone, it is necessary to associate the device with a different zone.
In fact, a device always belongs to a zone (default zone = 480).
The zone 480, in theory fully usable as the other zones, in practice covers the role of temporary storage area for the
devices just acquired by the panel at the end of an initialization procedure.
Therefore, it is advisable to move the devices just acquired by the panel from the zone 480 to other zones which the
user intends to use. For each of these zones the limit of 32 devices must not be violated.
If one or more devices are left into the zone 480, when returning in the scanning phase the control panel will
signal a field fault.