140
FAP54 Programming
7.2 APPENDIX 2 – FAULT CODES FOR CIRCUIT MODULE
If a circuit module undergoes a fault during the scanning phase, the control panel detects this fault and notifies the
user with this message:
FAULT CIRCUIT MODULE XX (YY)
XX
= module which underwent the fault
YY
= fault code
The table below reports the fault codes along with the relevant explanation:
Code
Fault
1
Access error to the non volatile memory of the module.
2
Program supervision error (1).
3
Fault in the output analog section of the module.
4
The module does not answer to commands.
5
Module removed.
6
Module reset.
7
Unexpected answer from the module (1).
8
Unexpected answer from the module (1).
9
Unexpected answer from the module (1).
10
Unexpected answer from the module (1).
11
Unexpected answer from the module (1).
12
Unexpected answer from the module (1).
13
Module is blocked (1).
14
Module not usable because of a serious line fault (e.g. short circuit, overload).
15
Fault in the module transmitter.
16
Fault in the module transmitter.
17
Data memory corrupted (1).
18
System memory corrupted (1).
19
System memory corrupted (1).
20
Code memory corrupted.
21
Non volatile memory corrupted (1).
(1) Please, contact the ELKRON Customer Service.
7.3 APPENDIX 3 – FAULT CODES FOR THE COMMAND AND CONTROL MODULE
If the Command & Control module undergoes a fault during the scanning phase, the user is notified with this message:
FAULT C&C MODULE (XX)
XX
= fault code
The table below reports the fault codes of the Command and Control module and the relevant explanation:
Code
Fault
1
Access error to the non volatile memory of the module.
2
Program supervision error (1).
3
Internal fault: 25 V voltage is low.
4
Internal fault: 25 V voltage is high.
5
Internal fault: 8 V voltage is low.
6
Internal fault: 8 V voltage is high.
7
Internal fault in RAM: data area corrupted.
8
Internal fault in NVM: wrong default data.
9
The module does not answer to the commands.
10
Module reset.
11
The module does not accept the command (1).
12
Module blocked (1).
(1) Please, contact the ELKRON Customer Service.