FAP54 Programming
95
DIP SWITCH 1/2/3
[1] # OFF
[2] ON
RESTORE DEFAULT VALUES
[1] YES
[2] # NO
[1] HOLD-OFF TIME
[2] LED ACTIVE
[3] FREQUENT BLINKING
[4] BASE BLINKING
[5] VOLUME
[6] TONES
[7] SYNCHRONIZED ACTIVATION
[8] DEFAULT
HOLD-OFF TIME: XXX
The assignment of values to the alarm thresholds is subject to the following restrictions:
the admitted range for each threshold is 4.0
20.0 mA
threshold 1 must be less than or equal to threshold 2; as a consequence, if threshold 1 is assigned a value
greater than the current value of threshold 2, the latter is forced to the new value of threshold 1; also, if
threshold 2 is assigned a value smaller than the current value of threshold 1, the latter is forced to the new
value of threshold 2.
Press keys
5, 6, 7
to set up the position of the dip-switches 1, 2, 3:
Press key
1
to assign the OFF position to the dip-switch.
Press key
2
to assign the ON position to the dip-switch.
Press
OK
to confirm the choice. By pressing
ESC
, you go back to the previous menu without modifying the current
value.
Press key
8
to restore the factory settings in the device configuration.
To restore default values press
1
.
The active option is signalled by # symbol.
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the current state.
The default parameters of current input module 4-20 mA are listed below:
LED ACTIVE:
YES
FREQUENT BLINKING:
YES
THRESHOLD 1:
6.4 mA
THRESHOLD 2:
8.8 mA
DIP SWITCH 1:
OFF
DIP SWITCH 2:
OFF
DIP SWITCH 3:
OFF
3.7.3.11 Configure sounder (OM, FW code 0165 and 0169)
The configuration menu is shown below:
Press
1
to set the Hold-Off time:
Enter the Hold-Off time in the range 0-255 seconds and confirm with
OK
.
Press
ESC
to discard the changes and go back to the previous menu.