48
FAP54 Programming
Z002 ID01 L04 D012 OM(J)
NAME:XXXXXXX
> PROG(A1): --------------------
PROG(A2): --------------------
Z002 ID05 L--- D---
DELAYED OUTPUT MODULES: ON
PROCEDURE COMPLETED
Using the
LF/RG
keys, the selected programming can take on one sequence, according to the following table which
shows the valid programming sequences for the generic output module, in the three instants T0, T1, T2 (regardless of
the alarm condition 1 or 2):
Programming allowed
T0
(x min)
T1
(y min)
T2
(z min)
String displayed in the
control panel
EMPTY
-
-
-
T0:--- T1:--- T2:---
T0_ON
ON
-
-
T0:ON T1:--- T2:---
T1_ON
-
ON
-
T0:--- T1:ON T2:---
T2_ON
-
-
ON
T0:--- T1:--- T2:ON
T0_ON_T1_OFF
ON
OFF
-
T0:ON T1:OFF T2:---
T0_ON_T2_OFF
ON
-
OFF
T0:ON T1:--- T2:OFF
T1_ON_T2_OFF
-
ON
OFF
T0:--- T1:ON T2:OFF
T0_OFF
OFF
-
-
T0:OFF T1:--- T2:---
T0_OFF_T1_ON
OFF
ON
-
T0:OFF T1:ON T2:---
T0_OFF_T2_ON
OFF
-
ON
T0:OFF T1:--- T2:ON
T0_OFF_T1_ON_T2_OFF
OFF
ON
OFF
T0:OFF T1:ON T2:OFF
The
UP/DOWN
keys make the selector move between alarm 1 and alarm 2 programming of the output module
displayed and move to the next or previous output module.
As a matter of fact, it is possible to program alarm 1 and alarm 2 timings only for the output modules associated to the
zone and programmed for alarm 1 or alarm 2 activation condition.
If an output module is currently programmed for fault or maintenance activation condition, it cannot be programmed
with delayed activation and the following screen is displayed:
Finally, if the coordinates of any module are not present in the currently selected position of the list of output modules
associated to the zone, the following screen is displayed:
In the example shown above, position 5 of the list of output modules associated to the zone is empty (therefore, it
does not contain any pair of valid coordinates of any output module).
Once the delayed programming in alarm 1 and alarm 2 of the output modules has been configured, it is necessary to
press
OK
in order to confirm the entered data. The following confirmation screen will be displayed for a couple of
seconds:
By pressing
ESC,
instead, the configuration entered up to that time will be discarded.