FAP54 Programming
77
[1] READ LOCAL DEVICE
[2] READ REMOTE DEVICE
[3] CONFIGURE LOCAL DEVICE
[4] CONFIGURE REMOTE DEVICE
[5] UPDATE DEVICE
[6] DEVICE REPLACEMENT
CIRCUIT: XX
DEVICE: XXX
TYPE: XX
[OK] CONTINUE [ESC] BACK
CIRCUIT: XX
CIRCUIT: XX
DEVICE: ---
COMMUNICATION ERROR
3.7 CONFIGURE DEVICES
Through this menu it is possible to configure the typical parameters of each device.
Unlike the menu described in
paragraph 3.4 DEVICE – DEVICES
PROGRAMMING
which mentioned the device
parameters concerning exclusively the control panel which were unknown by the device, this menu makes reference
to parameters which are not only stored in the control panel, but must be transmitted also to the device.
Through this menu it is also possible to program each device before it is installed on the detection line. The
programmed parameters (such as, for instance, address, type, etc.) are saved inside the device in a non volatile
memory. The device configuration menu is shown below:
[1] READ LOCAL DEVICE
This option makes it possible to read the address, the type and other typical parameters of a device connected locally
with the control panel.
[2] READ REMOTE DEVICE
This option makes it possible to check the programmed parameters of a device already configured and normally
connected to the detection circuit.
[3] CONFIGURE LOCAL DEVICE
This option makes it possible to configure the address, the type and other typical parameters of a device connected
locally with the control panel.
[4] CONFIGURE REMOTE DEVICE
This option makes it possible to set the type and other typical parameters of a device already configured and
connected with the detection circuit.
[5] UPDATE DEVICE
This option makes it possible to update a device on the field with the configuration stored in the control panel memory.
[6] DEVICE REPLACEMENT
This option makes it possible to change a faulty device inside the system with a brand new device.
3.7.1
Read local device
The reading of the device configuration parameters, such as address, type, revision and specific parameters, can be
carried out directly by the control panel.
Before accessing the related programming menu, connect the device directly with a circuit module.
Enter the number of the circuit connected with the device and confirm with
OK
:
The circuit will be powered on (possible line malfunctioning will be notified) and then the following screen view will be
displayed if the device is not present:
or the following if the device is correctly detected:
In this last case, the address and type of device will be displayed.
By pressing
OK
, a list of parameters depending on the type of device is displayed.
Summary of Contents for FAP54
Page 151: ...FAP54 Programming 151 ...