46
FAP54 Programming
ZONE:
DELAYED OUTPUT MODULES
[1] PROGRAMMING
[2] VERIFY
[ESC] BACK
To better understand this last point, an example can help. Consider the following table:
Position in the list of
modules associated
with the zone
Coordinates
of the module
PROGRAMMING TABLE
IN ALARM 1
T0(A1) = 1 min
T1(A1) = 2 min
T2(A1) = 3 min
PROGRAMMING TABLE
IN ALARM 2
T0(A2) = 0 min
T1(A2) = 2 min
T2(A2) = 5 min
ID
Circuit
Address
T0(A1)
T1(A1)
T2 (A1)
T0(A2)
T1(A2)
T2(A2)
1
1
12
---
---
ON
OFF
---
---
2
1
15
---
---
ON
---
ON
---
3
5
1
---
ON
OFF
OFF
ON
OFF
4
5
20
ON
---
OFF
OFF
ON
OFF
5
5
32
---
---
---
ON
---
---
…
…
50
---
---
When the zone goes to alarm 1:
no output module is activated because T0(A1) = 1 minute
after 1 minute (T0(A1) expired), the output module with ID = 4 (circuit = 5, address = 20) is activated
after 2 minutes (T1(A1) expired), the output module with ID = 3 (circuit = 5, address = 1) is activated
after 3 minutes (T2(A1) expired), the output modules with ID = 1 and ID = 2 are activated and the modules
with ID = 3 and ID = 4 are deactivated
Now suppose that after 3.5 minutes from the transition of the zone in alarm 1, the zone goes to alarm 2. In these
conditions, the programming table in alarm 2 is used, considering however the already elapsed time (3.5 mins) which
is between T1(A2) and T2(A2).
The output modules will be driven by taking into account the most recent action provided in the table, so:
the output module with ID = 1 will be deactivated according to the programming in T0(A2)
the modules with ID = 2, ID = 3 and ID = 4 will be activated according to the programming in T1(A2)
the module with ID = 5 will be activated according to the programming in T0(A2)
Referring once again to the same table, suppose now that the zone moves from idle to alarm 1 condition; when the
first minute elapses (T0(A1) expires) the output module with ID = 4 will be activated.
Now, suppose that after few seconds the zone goes to alarm 2; in this condition, by taking into account that the time
already elapsed (1 min and a few seconds) falls between T0(A2) and T1(A2), the modules with ID = 1, 3 and 4 will be
deactivated and the module with ID = 5 will be activated.
NOTES
:
the output modules for which delayed programming can be applied are the ones configured for alarm 1 or
alarm 2 activation.
The modules configured for fault or maintenance will be activated immediately when the relevant condition occurs.
The programming of the activation condition of a generic output module will be described in the paragraph “DEVICE”.
Insert and confirm with
OK
the number of the zone involved in the configuration of the delayed output modules
management:
The following menu is the displayed