FAP54 Programming
105
SLAVE ADDRESS: XXX
NAME: XXXXXXXXXXXX
EXTINGUISHMENT: YES /NO
EQUIPMENT TO BE RECOGNIZED /PRESENT
SLAVE ADDRESS:
EQUIPMENT DELETED
SLAVE ADDRESS: XXX
NAME: XXXXX
[OK] DELETE
[ESC] CANCEL
SLAVE ADDRESS:
SLAVE ADDRESS: XX
NAME: XXXXX
[[1] # INCLUDED
[2] EXCLUDED
Then, the following message will be displayed:
By pressing
ESC
you will go back to the address menu, so that another SLAVE control panel can be inserted.
The SLAVE control panels can be added even though they are not physically present. In fact, as soon as a new SLAVE
control panel is added, it is considered as “to be recognized”. The MASTER control panel will try to recognize the SLAVE
control panels added and not yet acquired once it returns to the scanning phase. When the SLAVE control panel is
connected to the MASTER/SLAVE network and is turned on, it will reply to the polling by the MASTER control panel and,
from that moment on, the SLAVE control panel has been recognized. If an already recognized SLAVE control panel is
disconnected by the network, the MASTER control panel detects the missing communication and generates a general fault.
Please note that in order for a SLAVE control panel to be successfully recognized it is necessary that the address
assigned to the SLAVE control panel by the MASTER is the same address assigned locally to the SLAVE control
panel through the suited menu (see
paragraph 3.8.4 Control Panel
).
DELETE
With this function it is possible to remove a SLAVE control panel from the list of SLAVE control panels controlled by a MASTER.
Enter the address of the SLAVE control panel to be removed and confirm with
OK:
After selection, the following screen view will be displayed:
To confirm removal, press
OK
, to cancel press
ESC.
If removal is confirmed, the following message will be displayed:
Press
ESC
to go back to the address menu for removing the next SLAVE control panel.
INCLUDE/EXCLUDE
With this function it is possible to temporarily exclude a SLAVE control panels controlled by the MASTER control
panel. Unlike removal, the exclusion allows to keep the address assigned to the SLAVE control panel for its
subsequent re-inclusion.
Enter the address of the SLAVE control panel to be excluded and then confirm with
OK
:
After entering the address, the following screen view will be displayed:
Select the required option ( The “#”symbol identifies the selected option) and confirm with
OK
.
The exclusion is signalled by the control panel LEDs and by a message shown during the scanning phase.
Moreover, in the case the programmable relay is programmed as the exclusion relay, the programmable relay is
activated. Any time an exclusion/inclusion occurs, an event is stored in the event log.
Summary of Contents for FAP54