FAP54 Programming
139
The following table contains the device error codes and the relevant explanation.
Code
Fault
1
Smoke/heat detector: internal fault of the optical section.
2
Smoke/heat detector: internal fault of the optical section (signal less than the fault threshold).
3
Internal fault of the temperature detection section.
4
Smoke detector: error at the end of the optical calibration procedure.
5
Smoke detector: optical calibration is missing because of out of range temperature.
6
Internal fault: non volatile memory access error.
7
Internal fault: testing not executed.
8
Internal fault: optical calibration not executed.
9
Internal fault: calibration failed.
10
Heat detector or smoke/heat detector: internal fault of the temperature detection section.
11
Manual call point: internal fault of the alarm switch.
12
External fault: analog input 1 is short circuited.
13
External fault: analog input 1 is open (end of line resistor is missing).
14
External fault; analog input 2 is short circuited.
15
External fault: analog input 2 is open (end of line resistor is missing).
16
External fault: missing short circuit of input 1 of a mode 2 actuator within the expected time (feedback time).
17
External fault: alarm repetition output is short circuited.
18
The device has notified an external fault, but it is not possible to read the cause because of a
communication problem.
19
Type programming error.
20
The device does not answer to the cyclic polling during the monitoring phase.
21
The device does not answer to a command.
22
The device does not answer to the initial polling at the beginning of the monitoring phase.
23
The device answers wrongly with a too high current to the polling during the monitoring phase (possible
answer coming simultaneously from more than one device).
24
The device type is different than the programmed one.
25
Device not accepted because of wrong manufacturer code.
26
The device does not answer to the adaptation command.
27
The device does not answer to the status request command for inclusion verification.
28
The device does not answer to the command of inclusion.
30
External fault: alarm repetition/siren output is open (end of line resistor is missing).
31
External fault: alarm repetition/siren output is short circuited.
32
External fault: electrical overloaded on the gemma output.
33
External fault: external power supply applied to a device programmed to work without it.
34
External fault: external power supply missing on a device programmed to work with it.
35
External fault: the value read is lower than the threshold of fault of the analog section (possible break of
the electric connection with the measurement equipment).
36
External fault: conventional detection circuit is short circuited.
37
External fault: conventional detection circuit is open (end of line resistor is missing).
38
Dip-switch configuration on the device is different than the one programmed in the control panel.
40 - 43
Failure of the attempt to recovery communication with the device after a missing answer to the cyclic
polling during the monitoring phase.
60
External device fault: analogue measurement above short circuit fault threshold.
61
External device fault:. analogue measurement lower fault threshold 1.2mA.
100
External device fault: manual interruption of the actuation.
101
External device fault: restoring of manual interruption of the actuation.
102
External device fault: actuation active but input 1 not short-circuited.
Summary of Contents for FAP54