30
FAP54 Programming
CONFIGURATION CIRCUIT: XX TYPE: XXXXX
TOT. DEVICES: XXX
XXX/SM XXX/HT XXX/OM XXX/CM
XXX/MN XXX/CI XXX/LN XXX/SH
CONFIGURATION CIRCUIT: XX TYPE: XXXXX
TOT. DEVICES: XXX
XXX/LI XXX/PI XXX/XS XXX/TB
XXX/GS XXX/IS XXX/ER XXX/??
CONFIGURATION STORED
[1] DELELE ALL THE ASSOCIATIONS
[2] DELETE EXPIRED ASSOCIATIONS
[ESC] BACK
WARNING! THIS PROCEDURE IS VALID ONLY
FOR DEVICES CONNECTED IN PURE PARALLEL
[OK] CONTINUE [ESC] BACK
PROCEDURE IN PROGRESS
********************************
[OK] FINISH [ESC] ABORT
PROCEDURE IN PROGRESS
PLEASE WAIT
N. DEVICES: XX [ESC] ABORT
During the execution of the procedure, a message with the progress status represented by the number of devices
recognized so far is shown:
At the end of the initialization in auto-addressed, pre-configured or update mode, the configuration of the circuit will be
displayed along with all the devices detected on the selected line, subdivided per quantity and type.
Type “ER” refers to devices with problems of communication with the control panel or to devices with duplicated
addresses.
Type “??” refers to a device whose address is recognized by the control panel, but whose type is not listed in the
control panel configuration.
By pressing
OK
, the new configuration will be confirmed and stored.
At the end of storage, it is possible to carry out the total cancellation of the associations or only of those no longer
valid (similar remarks to the ones made for the configuration of all the lines):
If the walk addressing mode is selected, a further confirmation will be asked to the user:
If the user confirms with
OK
, the procedure will be started and the following message displayed:
By pressing
ESC
, the procedure is interrupted and
the control panel cancels the circuit configuration
.
Cancellation is due to the fact that the path addressing mode changes the addresses of the devices in the field which
now are misaligned with a possible old configuration potentially restorable by the control panel.
By pressing
OK
, the control panel is informed that the procedure is finished (the operator has removed and then re-
inserted the various devices in the order he wanted them to be addressed).
Summary of Contents for FAP54
Page 151: ...FAP54 Programming 151 ...