34
FAP54 Programming
ADDR PR TYPE INFO1 INFO2 TST FA128
> 001 A XX XXXX XXXX ---
002 A XX XXXX XXXX ---
003 B XX XXXX XXXX ---
CONFIGURATION CIRCUIT: XX TYPE: XXXXX
TOT. DEVICES: XXX FA128
XXX/SM XXX/HT XXX/OM XXX/CM
XXX/MN XXX/CI XXX/LN XXX/SH
CONFIGURATION CIRCUIT: XX TYPE: XXXXX
TOT. DEVICES: XXX FA128
XXX/LI XXX/PI XXX/XS XXX/TB
XXX/GS XXX/IS XXX/ER XXX/??
FAULT ON CIRCUIT MODULE XX
ERROR CODE: YYY
FAULT OF CIRCUIT No.: XX
BMP1: 01234567 BMP2: 01234567
----**-- *-*-----
TYPE: XXXX A = D--- B = D---
Next to the total number of devices on the circuit, the model of the circuit module is displayed which can assume
the following values:
FA128
(module for FAP devices)
ML54
(ML54 FAP module)
By pressing again
OK
, the line is powered on and controlled.
If during the power on of the circuit a module fault occurs, the user will be informed on the occurred fault through
this screen view:
Appendix 2 contains a list of the possible error codes and the relevant explanation.
If a line error occurs (specifically regarding the field), the following message will be displayed:
Appendix 9 contains all the necessary information for interpreting the screen above.
If the line is powered on and works correctly, all the existing devices are displayed.
ADDR
refers to the device address.
PR
indicates the device presence and can have the following values:
LP
: the device is on a loop configured circuit
A
: the device is on branch A of an open configured circuit
B
: the device is on branch B of an open configured circuit
--:
the device is not present
TYPE indicates the type of device.
INFO1, INFO2 are data depending on the type of test carried out.
TST is the number of to the test currently in progress.
FA128
indicates the type of circuit module. These are the types of modules that can be viewed:
FA128
(module for FAP devices), as in the example
ML54
(ML54 FAP module)
To carry out tests on a device, select it through arrows
and
and then press key
>
.
On the display, TST section, the string “>00” will be viewed, meaning that test 0 for the selected device has
started.
To change the type of test press one of the keys shown in the table, while to exit press
<
.
Summary of Contents for FAP54