FAP54 Programming
135
C: XX P: XXX MEAS. ITVL: XXX MEASURE: X
NAME: XXXXXXXXXXXX
START TEST: DD/MM/YYYY HH/MM/SS
NSAMPLE: SAMPLE DD/MM/YYYY HH/MM/SS
CIRCUIT: XX DEVICE: XXX
CIRCUIT: XX DEVICE: XXX
WARNING! MONITORING ON THE CIRCUIT
WILL BE STOPPED
[OK] CONTINUE [ESC] BACK
[1] TEXTUAL VIEW
[2] GRAPHICAL VIEW
THRESHOLD 115
N : SAMPLE n
N+1: SAMPLE n+1
N+2: SAMPLE n+2
By selecting
1
, the stored data will be displayed as follows:
NSAMPLE
is the sample number (starting from 0); SAMPLE is the sample value.
To view the previous or next sample use keys
and
.
By selecting
2
in the selection menu, a chart will be created with the time progress of the acquired values.
In this chart press keys
<
and
>
to select whether to view the first 32, 64, 128, 256, 512 samples or the whole set of
1024 samples.
To go back to the previous menu press
ESC.
4.6.3.4 View alarm data
Through this option the user can view the measurements made by a device around an alarm device.
More precisely, if a device is in alarm condition, it is possible to view the 30 measurements before and the 30
measurements after the alarm.
The control panel collects the 60 measurements to be viewed by communicating directly with the device. To make this
communication possible, it is necessary to stop the line scanning.
Enter the coordinates of the device in alarm and confirm with
OK
:
The user is now requested to confirm the retrieval of data:
By pressing
OK
to continue, the data will be collected from the device. During this operation the monitoring on the
circuit is interrupted.
At the end of this operation, the following screen view will be displayed:
If you select the text view, the list of samples will be displayed along with the alarm threshold:
Using the
and
keys you move to the previous or next group of 3 samples.
If the graphical view is selected, the samples will be displayed as a histogram where the generic sample can be
highlighted through keys
<
and
>
.
Summary of Contents for FAP54
Page 151: ...FAP54 Programming 151 ...