FAP54 Programming
47
DELAYED OUTPUT MODULES
[1] ENABLE
[2] DISABLE
#T0(A1): 1 m T1(A1): 3 m T2(A1): 4 m
T0(A2): 1 m T1(A2): 2 m T2(A2): 3 m
Z002 ID01 L04 D012 OM(C)
NAME:XXXXXXX
# PROG(A1): T0:--- T1:--- T2:---
PROG(A2): T0:--- T1:--- T2:---
3.2.4.1 Programming of delayed output modules
By selecting [1] PROGRAMMING, the following menu is displayed:
By selecting [1] ENABLE, the delayed output modules management functionality is enabled for the selected
zone and the following screen is displayed:
This menu makes the user configure T0, T1 and T2 timers both in alarm 1 and alarm 2 condition.
By using the arrow keys
LF/RG,
move the selector on the previous or next timer; with the
UP/DOWN
keys, the
current value of the timer can be set.
Please note that when a specific value of a timer is set, the control panel will automatically change the value of
the remaining timers in order to satisfy the constraints described before and reported below for convenience:
T0 < T1 < T2
T0 programming range 0, 8 minutes – boundaries included
T1 programming range 1, 9 minutes – boundaries included
T2 programming range 2, 10 minutes – boundaries included
By pressing
OK
, the following screen with the configuration of the programming tables in alarm 1 and alarm 2 of the
output modules associated to the zone is shown:
where:
Z002
= number of the zone involved in the programming
ID01
= identification of the current position of the list of output modules associated to the zone (when this screen is
shown for the first time, the information of the first element of the list is displayed)
L04, D012
= circuit and address of the output module under programming
OM(C)
= device type (output module) and its specialization (C/G/J/T) – for further information on module
specialization, please refer to the section “DEVICE” below in the document
NAME: XXXXX
= name of the output module
PROG(A1), PROG(A2)
= programming of alarm 1 and alarm 2 timings for the selected output module
The selector “#” indicates the programming (in alarm 1 or alarm 2) which can be currently modified.