FAP54 Programming
21
2.5 INDICATORS, KEYS, RELAYS, JUMPERS
2.5.1 Front side indicators
INDICATOR
COLOR
FUNCTION
A
L
A
R
M
S
FIRE ALARM
RED
Blinking:
the control panel is in alarm condition and the siren output is not
active
Fixed ON:
the control panel is in alarm condition and the siren output is active
MASTER ALARM
RED
When turned ON, a general alarm condition has occurred.
C
O
M
M
U
N
IC
A
T
O
R
COMMUNICATOR
ACTIVE
RED
With communicator inserted
:
Blinking
: ongoing alarm transmission from E type communicator towards the
fire alarm receiving centre.
Steady ON
: ACK alarm received from the fire alarm receiving centre via E type
communicator.
Steady OFF: no alarm transmitted yet.
COMMUNICATOR
STATE
YELLOW
With communicator inserted
:
Blinking
: communicator fault.
Steady ON
: communicator excluded.
F
A
U
L
T
S
GENERAL
YELLOW
When turned ON, it indicates a fault condition. Further information on the type
of fault is provided through the display and the dedicated LEDs. This LED
provides a cumulative fault indication.
SYSTEM
YELLOW
When turned ON, it indicates a system fault. Usually, when this LED is ON it
indicates a fault affecting the functionality the CPU of the control panel.
BATTERY
YELLOW When ON, it indicates a control panel battery fault or malfunctioning.
SIREN
YELLOW
When ON, it indicates a fault on the line controlling the siren or a fault on an
actuator driving an alarm signalling device (“C” type)
EARTH
YELLOW When ON, it signals an earth dispersion.
M
A
IN
T
E
N
A
N
C
E
MAINTENANCE YELLOW
When ON, it indicates that the “self-adjustment” procedure has found one or
more optical smoke detectors which require maintenance.
TEST SYSTEM
YELLOW
When ON, it indicates that a zone test is in progress or that the periodic
maintenance is in progress.
MAIN/BATTERY
GREEN
Steady ON
: the control panel is powered on by the main AC
Blinking
: the control panel is powered on by batteries
E
X
C
L
U
S
IO
N
S
LINE
YELLOW When ON, it indicates that one or more circuits are excluded.
ZONE
YELLOW When ON, it indicates that one or more zones are excluded.
GROUP
YELLOW
When ON, it indicates that one or more groups of devices or groups of zones
are excluded.
DEVICE
YELLOW When ON, it indicates that one or more devices are excluded.
SIREN
YELLOW
When ON, it indicates the exclusion of a siren or an actuator driving an alarm
signaling device (“C” type).
ACTUATORS
YELLOW
When ON, it indicates the exclusion of an actuator driving fire-extinction
equipment (“G” type).
G
E
N
E
R
A
L
EXCLUSION
YELLOW
When ON, it indicates that something is excluded in the control panel.
This is an exclusion cumulative indicator.
REMOTE DEVICE YELLOW
When ON, it indicates a communication error during communication with an
LCD annunciator or a SLAVE control panel, or a communication problem
during communication with a PC via LAN.
SILENCE SIREN YELLOW
When ON, it indicates that the siren output has been turned off by using the
SILENCE SIREN
key.
ACTION
DELAYED
YELLOW
When ON, it indicates that the timer of a zone or group in time mode is running
or has expired and the zone or group has undergone an alarm condition.