131
P o l l i n g t h e T C U
Notes:
The information is sorted by register number in ascending order.
Labels in italics indicate differences between the standard TCU and the VFD-TCU (specifically registers 12550-12554).
Additional Modbus registers are used in the VFD-TCU and are listed at the end of the table.
Alarm states are listed for some but not all of the TCU’s I/O points. Those listed are common alarms, but any or all
configured telemetry points can be set to alarm in any desired state.
For analog input (AI) and output (AO) points, the Low State Label column gives the point’s Low Engineering value
followed by its Low Raw value; the High State Label column gives the point’s High Engineering value followed by its
High Raw value.
Register Label
Type Low State
Label
High State
Label
Resolution/
Units
Alarm
State
Description
1
Battery Test
DO
OFF
ON
ON
Control point used to turn off
the TCU’s AC power and go
to battery power
520
Station
Disable
DO
OFF
ON
In the ON state, allows
telemetry to remove power
from all pump motors
1025
Pump 1
Disable
DO
OFF
ON
In the ON state, allows
telemetry to cut power to
Pump 1
1026
Pump 2
Disable
DO
OFF
ON
In the ON state, allows
telemetry to cut power to
Pump 2
1027
Pump 3
Disable
DO
OFF
ON
In the ON state, allows
telemetry to cut power to
Pump 3
1028
Pump 1
Override
DO
OFF
ON
In the ON state, allows
telemetry to control Pump 1
and bypass the TCU
1029
Pump 2
Override
DO
OFF
ON
In the ON state, allows
telemetry to control Pump 2
and bypass the TCU
1030
Pump 3
Override
DO
OFF
ON
In the ON state, allows
telemetry to control Pump 3
and bypass the TCU
1537
Reserved
DO
Factory use only. Do not use.
1793
Aux Out
Override On
DO
OFF
ON
In the ON state, allows
telemetry to control the
auxiliary output
1794
Alarm Light
Override
DO
OFF
ON
In the ON state, allows
telemetry to control the alarm
light
1795
Alarm Horn
Override
DO
OFF
ON
In the ON state, allows
telemetry to control the alarm
horn
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......