112
A p p e n d i x H
CT Function = Direct Input
1. 3-Phase current imbalance (smoothed realtime)
2. Average current (smoothed realtime)
3. Minimum current measured in the last 24 hours
4. Maximum current measured in the last 24 hours
Alarms
None of the faults triggered from this module interrupt the pump control operation - they are warnings only (sent via
telemetrey) and notice on GUI.
Configuration
Description
Stops Pumps?
Disable
Amp 1 Fault
Triggers when the AMPS reading goes above
the overcurrent limit (% of FLC 1) or below
the undercurrent limit (% of FLC 1).
Also acts as the singular AMPS fault for
Direct Input mode.
No
Set FLC 1 = 0
Amp 2 Fault
Triggers when the AMPS reading goes above
the overcurrent limit (% of FLC 2) or below
the undercurrent limit (% of FLC 2).
No
Set FLC 2 = 0
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......