Motor Starter Circuit Wiring
Simplex stations use only MTR1_STR. Duplex stations use MTR1_STR and MTR2_STR. Triplex stations use all of the
motor starter outputs. Unused starter outputs can be used as auxiliary outputs with control provided by telemetry.
Alarm Light and Horn Outputs
The alarm outputs use mechanical relays to drive up to 0.5 A at 120 VAC or 1 A at 0-24 VDC. The addition of 1 A slow
blow fuses on the TCU outputs is recommended to protect the TCU’s alarm relays from short circuits. The alarm light
output is a set of contacts that are closed when the TCU is powered down.
The alarm light output is designed to energize an incandescent lamp. Any other application requires an
interposing relay, especially strobe lights due to their high peak current demands.
Alarm Horn and Alarm Light Wiring
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......