O p e r a t i n g P r o c e d u r e s
High Float (Disabled/Enabled)
If a high level float is being used, High Float must be enabled. If a high level float
is not connected and High Float is enabled, there is no effect on the operation of the
TCU. In a Pump Down Mode (Lift Station) system, all pumps are stagger-started
on a high float condition. In a Pump Up Mode (Storage Tank) system, all pumps are
stopped on a high float condition. A high float condition generates a high well alarm
and an optional transducer fault alarm.
Low Float (Disabled/Enabled)
If a low level float is being used, Low Float must be enabled. Low Float must be
disabled if a low level float is not connected. (If Low Float is not disabled, the
Low Well alarm will interfere with station operation.) In a Pump Down Mode (Lift
Station) system, all pumps are stopped on a low float condition. In a Pump Up
Mode (Storage Tank) system, all pumps are stagger-started on a low float condition.
A low float condition generates a low well alarm and an optional transducer fault
alarm.
XDCR High Float Fault
(Disabled/Enabled)
When this option is enabled, a high float condition generates a transducer fault and
switches control to the configured fault mode. Leaving the option disabled leaves
pump control on the primary transducer whenever a high float condition occurs or
the transducer reaches or exceeds 20 mA.
XDCR Low Level Fault
(enabled/disabled)
When this option is enabled, a low float condition OR a transducer low level
condition (level drops below Low set point) generates a transducer fault and
switches control to the configured fault mode. Leaving the option disabled leaves
pump control on the primary transducer whenever a low float or transducer low
level condition occurs.
High Float Override (Disabled/
Enabled)
When this option is enabled, the High Float is given precedence in the event of an
Off float failure when the TCU is in Float control mode (this can be a floats-only
system or an analog transducer system that uses floats for backup).
Options under the Radio Menu are used to configure the
TCU800’s station address and radio protocol settings.
Radio
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......