29
S e t u p
Wiring AC Power (typical 480 V, 3-wire transformer)
Motor Starter Outputs
1. Connect control power to the STR_PWR terminal (P1-24).
2. Connect the MTR1_STR terminal (P1-23) through a 1 A slow-blow fuse to the coil of the motor starter or the control
relay designated as Pump 1. (This fuse protects the TCU relays from short-circuited coils).
3. Connect the other side of the motor starter coil through appropriate disabling contacts to control power neutral. Make
similar connections for Pump 2 and Pump 3 for duplex and triplex stations.
When the alternator function is disabled through the TCU’s configuration, MTR1_STR controls the Lead pump, MTR2_
STR controls the Lag pump, and MTR3_STR controls the Lag2 pump. They should be wired accordingly.
Wiring AC Power (typical 240 V, 4-wire transformer)
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......