107
A d d i n g a R I O t o t h e T C U
For a RIO032 using all 32 I/O points, add the following:
Module Letter
Module Type (Number of I/O Points)
Module H
DMM (8 digital input points)
Module I
DCM (8 digital output points)
Module J
AMM (4 analog input points)
Module K
AMM (4 analog input points)
Module L
ACM (4 analog output points)
Module M
ACM (4 analog output points)
If you are using an HMI other than HT3, you will need to configure that software with the correct Modbus register
information for the RIO’s additional I/O.
Module Letter
Module Type (Number of I/O Points) Modbus Registers Used for Polling
Module H
DMM (8 digital input points)
14337 - 14344
Module I
DCM (8 digital output points)
2305 - 2312
Module J
AMM (4 analog input points)
35505 - 35508
Module K
AMM (4 analog input points)
35761 - 35764
Module L
ACM (4 analog output points)
44065 - 44068
Module M
ACM (4 analog output points)
44321 - 44324
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......