52
C h a p t e r 6
Options under the Alarm Output Menu are used to configure the
parameters of the Alarm Horn and Alarm Light features.
Auto Retry
The TCU can be configured to retry a faulted pump - one that fails to start when
called (Motor Start Fault) or one that is running when it has not being called to run
(Motor Stop Fault). The TCU’s responses to Motor Start Faults and Motor Stop
Faults with the Auto Retry function enabled are identical. The response to Motor
Stop Faults differs if the Auto Retry function has been disabled.
Alarm Output
Alarm Horn (Disabled/
Enabled)
When Alarm Horn is enabled, alarms are reported both at the station and through
telemetry. If there are active alarms when the TCU’s alarm horn option is enabled,
the alarm horn will not sound until the existing alarms have cleared and a new alarm
occurs. Disabling the alarm horn option does not prevent alarms from being reported
via telemetry.
Alarm Light (Disabled/
Enabled)
When the alarm light option is enabled, alarms are reported both at the station and
through telemetry. Disabling the alarm light option does not prevent alarms from
being reported via telemetry.
Options under the Float Menu are used to configure the faults
associated with high and low float conditions.
Floats
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......