86
A p p e n d i x B
11. Verify, as the LAG1 and LAG2 inputs are toggled, that the TCU starts additional pumps that the level input demands.
Allow for some delay on pump start after the level input is activated.
12. After the system is checked out, connect the backup battery, if used. Make sure the battery is properly connected.
Observe polarity markings.
13. If the battery is charged, cycle the TCU’s AC power off and verify battery backup operation. Make sure to turn the TCU
on when finished with the checkout procedure.