J. Polling the TCU - DFS Point and Modbus Registers
Pump Control Application by Module Letter and Point
The TCU Pump Control template consists of eight individual modules, including one for the integrated radio. The tables on
the following pages list the properties of each module contained in the template and provide a description of each point’s
function.
For those systems using the Modbus protocol, equivalent Modbus registers are also provided.
Note:
Alarm states are listed for some but not all of the TCU’s I/O points. Those listed are common alarms, but any or all
configured telemetry points can be set to alarm in any desired state.
Module A - DMM002
Point # Point Name
Point
Type
Modbus
Register
Low State
Label
High State
Label
Alarm
State
Description
1
Pump 1 Status DI
12545
OFF
RUNNING
Detects the state of Pump 1
2
Pump 2 Status DI
12546
OFF
RUNNING
Detects the state of Pump 2
3
Pump 3 Status DI
12547
OFF
RUNNING
Detects the state of Pump 3
4
Phase Monitor
Bypass
DI
12548
OFF
ON
Detects if the phase monitor
bypass is OFF or ON
5
Low Float
Input
DI
12549
OFF
ON
Detects the state of the Low
Float
6
Off Float
Input*
DI
12550
OFF
ON
Detects the state of the Off
float
7
Lead Float
Input*
DI
12551
OFF
ON
Detects the state of the Lead
float
8
Lag Float
Input*
DI
12552
OFF
ON
Detects the state of the Lag
float
9
Lag2 Float
Input*
DI
12553
OFF
ON
Detects the state of the Lag2
float
10
High Float
Input*
DI
12554
OFF
ON
Detects the state of the High
float
11
Any Pump
DI
12555
OFF
RUNNING
Detects the status of any
pump in the telemetry system
12
Auxiliary
Input
DI
12556
OFF
ON
Detects the state of the
Auxiliary input
*For VFD operation, these inputs are reserved as spare I/O.
Module B - DCM001
Point # Point Name
Point
Type
Modbus
Register
Low State
Label
High State
Label
Alarm
State
Description
1
Starter 1 Out* DI
12801
OFF
ON
Detects the state of pump
starter 1
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......