P r o d u c t O v e r v i e w
Bottom Connector 1: P2
PIN#
Name
Description
Electrical Rating
Module
Address
P2-1
MTR1_RUN Motor 1 run digital monitor input
10-30VAC/DC, 10mA
A1
P2-2
MTR2_RUN Motor 2 run digital monitor input
10-30VAC/DC, 10mA
A2
P2-3
MTR3_RUN Motor 3 run digital monitor input
10-30VAC/DC, 10mA
A3
P2-4
EXT_PM
External phase monitor digital monitor input
10-30VAC/DC, 10mA
A4
P2-5
IN_COM_1
Common return for motor run and external phase
monitor input
10-30VAC/DC, 100mA
RTN
--
P2-6
LOW_LVL
Low Level digital monitor input
10-30VAC/DC, 10mA
A5
P2-7
OFF_LVL
Off Level digital monitor input
10-30VAC/DC, 10mA
A6
P2-8
LEAD_LVL Lead Level digital monitor input
10-30VAC/DC, 10mA
A7
P2-9
LAG1_LVL
Lag1 Level digital monitor input
10-30VAC/DC, 10mA
A8
P2-10 LAG2_LVL
Lag2 Level digital monitor input
10-30VAC/DC, 10mA
A9
P2-11 HIGH_LVL
High Level digital monitor input
10-30VAC/DC, 10mA
A10
P2-12 AUX_IN
Auxiliary digital monitor input; supports pulse count-
ing
10-30VDC, 10mA
A12
P2-13 ALM_SIL
Alarm Silence Switch digital monitor input
10-30VAC/DC, 10mA
B7
P2-14 IN_COM_2
Common return for input level, aux inputs, and alarm
silence switch
10-30VAC/DC, 100mA
RTN
--
P2-15 ISOGND
Internally supplied 24VDC bias source return (isolated) <24V / Not Rated
--
P2-16 ISO+24V
Internally supplied 24VDC bias source voltage (isolat-
ed)
<24V / Not Rated
B10
P2-17 TXD_232
RS-232 transmit data to external device
<24V / Not Rated
--
P2-18 RXD_232
RS-232 receive data from external device
<24V / Not Rated
--
P2-19 GND
RS-232 ground
<24V / Not Rated
--
P3-12 SHUNT
250Ω shunt resistor; jump to P3-11 to use a 4-20mA
signal for (P3-10)
<24V / Not Rated
P3-13 SHIELD
Internally connected to chassis ground; cable shield
for analog monitor signals
Ground
P3-14 IN_COM_3
Common return for thermal and seal failure digital
outputs
10-30VAC/DC, 100mA
RTN
P3-15 MTR3_
THERM
Motor 3 temperature monitor input
10-30VAC/DC, 10mA
H6*
P3-16 MTR2_
THERM
Motor 2 temperature monitor input
10-30VAC/DC, 10mA
H5*
P3-17 MTR1_
THERM
Motor 1 temperature monitor input
10-30VAC/DC, 10mA
H4*
P3-18 MTR3_SEAL Motor 3 moisture seal monitor input
10-30 VAC/DC, 10mA
H3*
P3-19 MTR2_SEAL Motor 2 moisture seal monitor input
10-30 VAC/DC, 10mA
H2*
P3-20 MTR1_SEAL Motor 1 moisture seal monitor input
10-30 VAC/DC, 10mA
H1*
*When the new I/O is enabled, it will move to the next available module if H and I are already configured.
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......