P o l l i n g t h e T C U
8
Pump 2 Starter DI
13320
NORMAL
FAULT
FAULT Allows telemetry to sense a
Pump 2 starter failure and
activate the alarm
9
Pump 3 Starter DI
13321
NORMAL
FAULT
FAULT Allows telemetry to sense a
Pump 3 starter failure and
activate the alarm
10
Pump 1 Stop
DI
13322
NORMAL
FAULT
FAULT Allows telemetry to sense
a Pump 1 stop failure and
activate the alarm
11
Pump 2 Stop
DI
13323
NORMAL
FAULT
FAULT Allows telemetry to sense
a Pump 2 stop failure and
activate the alarm
12
Pump 3 Stop
DI
13324
NORMAL
FAULT
FAULT Allows telemetry to sense
a Pump 3 stop failure and
activate the alarm
Module E - ACM001
Point # Point Name
Point
Type
Modbus
Register
Low State
Label*
High State
Label**
Alarm
State
Description
1
Remote Level AO
42273
4/820
20/4095
0.01/mA Calibration point for
displaying level for a remote
input
2
Unused
3
Unused
4
Well Level
AO
42276
0/0
60/600
0.1/FT
Calibration point for
displaying well level
* For analog points, the Low State Label column gives the point’s Low engineering value followed by its Low raw value.
** For analog points, the High State Label column gives the point’s High engineering value followed by its High raw value.
Module F - DCM001
Point # Point Name
Point
Type
Modbus
Register
Low State
Label
High State
Label
Alarm
State
Description
1
RESERVED
DO
1537
OFF
ON
RESERVED
2
Low Well
Level
DI
13826
NORMAL
ALARM
ALARM Detects state of Low level
sensor
3
High Well
Level
DI
13827
NORMAL
ALARM
ALARM Detects state of High level
sensor
4
HOA 1
DI
13828
-
HAND
HAND
Detects position of HOA 1
switch and activates alarm for
“Hand” position
5
HOA 1
DI
13829
-
OFF
OFF
Detects position of HOA 1
switch and activates alarm for
“Off” position
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......