132
A p p e n d i x J
1796
Aux Out
Disable
DO
OFF
ON
Detects if the auxiliary output
is in the auto or disabled state
1797
Alarm Light
Disable
DO
OFF
ON
Detects if the alarm light is in
the auto or disabled state
1798
Alarm Horn
Disable
DO
OFF
ON
Detects if the alarm horn is in
the auto or disabled state
1799
Pump
Override
Reset
DO
OFF
ON
When set, allows the Off level
input to reset pump overrides
1800
Analog
Updating
DO
OFF
ON
This is a legacy PCU function,
and only applies to a TCU
being used as a PCU. It has
no application in a standard
TCU installation. This setting
is an on/off switch for logging
analog values. It enables the
TCU to respond with full
analog status each time it is
polled. This setting should
be used judiciously as it will
have a large impact on the
radio polling rate.
12299
Bias Voltage DI
OFF
ON
OFF
Detects the presence of
isolated DC bias and activates
the alarm when absent.
12300
TCU Power
DI
OFF
ON
OFF
Detects the presence of AC
power and activates the alarm
when absent.
12545
Pump 1
Status
DI
OFF
RUNNING
Detects the state of pump 1
12546
Pump 2
Status
DI
OFF
RUNNING
Detects the state of pump 2
12547
Pump 3
Status
DI
OFF
RUNNING
Detects the state of pump 3
12548
Phase
Monitor
Bypass
DI
OFF
ON
Detects if the phase monitor
bypass is OFF or ON
12549
Low Float
Input
DI
OFF
ON
Detects the state of the Low
float
12550
Off Float
Input Spare
I/O (VFD)
DI
OFF
ON
Detects the state of the Off
float (Spare I/O in VFDTCU
application).
12551
Lead Float
Input Spare
I/O (VFD)
DI
OFF
ON
Detects the state of the Lead
float (Spare I/O in VFD-TCU
application).
12552
Lag Float
Input Spare
I/O (VFD)
DI
OFF
ON
Detects the state of the Lag
float (Spare I/O in VFDTCU
application)
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......