135
P o l l i n g t h e T C U
13835
HOA 3
DI
-
OFF
OFF
Detects position of HOA 3
switch and activates alarm for
“Off” position
13836
HOA 3
DI
-
AUTO
Detects position of HOA 3
switch and activates alarm for
“Auto” position
32945
Reserved
AI
Factory use only. Do not use.
32946
Reserved
AI
Factory use only. Do not use.
32947
Internal
Temperature
AI
0/32
100/212
0.1/F
Detects the TCU’s internal
temperature
33713
Analog Input
1
AI
4/820
20/4095
0.01/mA
Settings for the primary
analog input
33714
Analog Input
2
AI
4/820
20/4095
0.01/mA
Settings for the auxiliary
analog input
33715
Phase AB
Voltage (240
VAC)
AI
0/350
300/3102
1/VAC
Settings for Phase AB voltage
for 240 VAC 1- or 3-phase
monitor
33715
Phase AB
Voltage (480
VAC 3-phase)
AI
0/350
600/3114
1/VAC
Settings for Phase AB voltage
for 480 VAC 3-phase monitor
33716
Phase AC
Voltage (240
VAC)
AI
0/350
300/3077
1/VAC
Settings for phase AC voltage
for 240 VAC 1- or 3-phase
monitor
33716
Phase AC
Voltage (480
VAC 3-phase)
AI
0/350
600/3077
1/VAC
Settings for phase AC voltage
for 480 VAC 3-phase monitor
42273
Remote Level AO
4/820
20/4095
0.01/mA
Calibration point for
displaying the level for a
remote input
42276
Well Level
AO
0/0
60/600
0.1/FT
Calibration point for
displaying well level
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......