A p p e n d i x H
CT Rating
The maximum current the CTs will read when
outputting 333 mVAC.
If the CTs being used do not output
333mVAC at full scale, they can either
not be used or a calculation must be done
to determine what the current would be at
333mVAC. The maximum voltage the TCU
CT Inputs can read is 353 mVAC.
5 - 100
100
Full Load Current 1
The average current drawn from pump 1 (or
the station if in Direct Input mode) while
running at full capacity. This setting is used to
determine the thresholds for the undercurrent
and overcurrent alarms. Alarming can be
disabled by setting this to 0.
0 - 100
0
Full Load Current 2
The average current drawn from pump 2
while running at full capacity. This setting
is used to determine the thresholds for
the undercurrent and overcurrent alarms.
Alarming can be disabled by setting this to 0.
0 - 100
0
Full Load Current 3
The average current drawn from pump 2
while running at full capacity. This setting
is used to determine the thresholds for
the undercurrent and overcurrent alarms.
Alarming can be disabled by setting this to 0.
0 - 100
0
Undercurrent Alarm
The percentage of Full Load Current where
an undercurrent alarm is generated. Can be
disabled with 0.
0 - 99%
3%
Overcurrent Alarm
The percentage of Full Load Current where an
overcurrent alarm is generated.
100 - 200%
110%
Imbalance Alarm
The maximum allowable percentage of phase
to phase current imbalance before an alarm is
generated. Can be disabled with 0.
0 - 200%
25%
Summary of Contents for TCU800
Page 1: ...Installation and Operation Manual T C U 8 0 0 Data Flow Systems Inc P r e l i m i n a r y ...
Page 2: ...Intentionally left blank ...
Page 4: ...D a t a F l o w S y s t e m s I n c Intentionally left blank ...
Page 8: ...ii Intentionally left blank ...
Page 10: ...ii Intentionally left blank ...
Page 56: ...46 C h a p t e r 5 Quick View Analog View Pump Statistics ...
Page 57: ...47 U s e r I n t e r f a c e Alarms Settings Screen 1 Settings Screen 2 ...
Page 58: ...48 C h a p t e r 5 Advanced Settings About ...
Page 77: ...67 O p e r a t i n g P r o c e d u r e s TCU Installed in Existing Control Panel ...
Page 87: ...77 M o d b u s S u p p o r t Figure 1 Figure 2 Figure 3 ...
Page 92: ...82 D a t a F l o w S y s t e m s I n c Appendix ...
Page 157: ...147 D a t a F l o w S y s t e m s I n c ...
Page 158: ...148 D a t a F l o w S y s t e m s I n c ...
Page 159: ...149 D a t a F l o w S y s t e m s I n c ...
Page 160: ......