[61]
Counter A
(down)
Input for decrement counting in the SLC counter.
[62]
Reset Counter
A
Input for reset of counter A.
[63]
Counter B (up)
Input for increment counting in the SLC counter.
[64]
Counter B
(down)
Input for decrement counting in the SLC counter.
[65]
Reset Counter B Input for reset of counter B.
[101] Sleep
A signal applied puts the drive into sleep mode.
[120] Lead Pump
Start
A signal applied puts the lead pump into start mode.
[121] Lead Pump Al-
ternation
A signal applied puts the lead pump into alternation mode.
[130] Pump 1 Inter-
lock
A signal applied puts pump 1 into interlock mode.
[131] Pump 2 Inter-
lock
A signal applied puts pump 2 into interlock mode.
[132] Pump 3 Inter-
lock
A signal applied puts pump 3 into interlock mode.
[133] Pump 4 Inter-
lock
A signal applied puts pump 4 into interlock mode.
[134] Pump 5 Inter-
lock
A signal applied puts pump 5 into interlock mode.
[190] Fire Mode Ref
Bit 0
Enable a selection of 1 of the 8 fire mode references according to
.
[191] Fire Mode Ref
Bit 1
Enable a selection of 1 of the 8 fire mode references according to
.
[192] Fire Mode Ref
Bit 2
Enable a selection of 1 of the 8 fire mode references according to
.
4.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals.
5-30 Terminal 27 Digital Output
Default value: [0] No operation
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the function for terminal 27 digital output.
Table 138: Option:
[0]
No operation
No operation.
[1]
Control Ready
The control board receives supply voltage.
[2]
Drive ready
The drive is ready for operation and applies a supply signal on the control board.
AU363928304090en-000101 / 130R0982 | 79