Select the input at which the thermistor (PTC sensor) should be connected. When using an analog input, the same analog cannot be
used as a reference in
parameter 3-15 Reference Resource 1
to
parameter 3-17 Reference Resource 3
,
parameter 20-00 Feedback 1 Source
,
parameter 20-03 Feedback 2 Source
,
parameter 24-06 Fire Mode Reference Source
, and
parameter 24-07 Fire Mode Feedback Source
.
Table 86: Option:
[0]
None
Do not set thermistor source.
[1]
Analog input AI53
Use analog input 53 as thermistor source.
[6]
Digital input 29
Use digital input 29 as thermistor source.
4.4 Parameter Group 2-** Brakes
4.4.1 2-0* DC-Brake
Parameters for configuring the DC brake and DC hold functions.
2-00 DC Hold/Motor Preheat Current
Default value: 50%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
N O T I C E
MOTOR OVERHEATING
The maximum value depends on the rated motor current.
To avoid motor damage caused by overheating, do not run at 100% for too long.
Set holding current as a percentage of the rated motor current I
M,N
in
parameter 1-24 Motor Current
.
Parameter 2-00 DC Hold/Motor
Preheat Current
holds the motor function (holding torque) or pre-heats the motor. This parameter is active if DC hold is selected in
parameter 1-72 Start Function
[0] DC Hold/delay time
or
parameter 1-80 Function at Stop
[1] DC hold/Motor Preheat
.
Table 87: Range:
Min: 0%
Max: 160%
Default value: 50%
2-01 DC Brake Current
Default value: 50%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
N O T I C E
MOTOR OVERHEATING
The maximum value depends on the rated motor current.
To avoid motor damage caused by overheating, do not run at 100% for too long.
Set current as % of rated motor current,
parameter 1-24 Motor Current
. When speed is below the limit set in
parameter 2-04 DC Brake
Cut In Speed
, or when the DC-brake inverse function is active (in
parameter group 5-1* Digital Inputs
set to
[5] DC-brake inverse
; or via
the serial port), a DC brake current is applied on a stop command. See
parameter 2-02 DC Braking Time
for duration.
Table 88: Range:
Min: 0%
Max: 150%
Default value: 50%
2-02 DC Braking Time
Default value: 10 s
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
AU363928304090en-000101 / 130R0982 | 57
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide