[32] SL Time-out 2
Use the result of timer 2 in the logic rule.
[33] Digital input DI18
Use the value of DI18 in the logic rule (High = True).
[34] Digital input DI19
Use the value of DI19 in the logic rule (High = True).
[35] Digital input DI27
Use the value of DI27 in the logic rule (High = True).
[36] Digital input DI29
Use the value of DI29 in the logic rule (High = True).
[39] Start command
This logic rule is True if the drive is started by any means (either via digital input, or other).
[40] Drive stopped
This logic rule is True if the drive is stopped or coasted by any means (either via digital input, or
other).
[42] Auto Reset Trip
This logic rule is True if the drive is tripped (but not trip-locked) and an automatic reset is issued.
[50] Comparator 4
Use the result of comparator 4 in the logic rule.
[51] Comparator 5
Use the result of comparator 5 in the logic rule.
[60] Logic rule 4
Use the result of logic rule 4 in the logic rule.
[61] Logic rule 5
Use the result of logic rule 5 in the logic rule.
[70] SL Time-out 3
Use the result of timer 3 in the logic rule.
[71] SL Time-out 4
Use the result of timer 4 in the logic rule.
[72] SL Time-out 5
Use the result of timer 5 in the logic rule.
[73] SL Time-out 6
Use the result of timer 6 in the logic rule.
[74] SL Time-out 7
Use the result of timer 7 in the logic rule.
[81] Dry Pump
A dry-pump condition has been detected. Enable this function in
parameter 22-26 Dry Pump Func-
tion
.
[82] End of Curve
An end-of-curve condition has been detected. Enable this function in
parameter 22-50 End of Curve
Function
.
[83] Broken Belt
A broken-belt condition has been detected. Enable this function in
parameter 22-60 Broken Belt
Function
.
4.10.5 13-5* States
Parameters for programming the smart logic controller.
13-51 SL Controller Event
Default value: [0] False
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select the boolean input (True or False) to define the smart logic controller event. See
parameter 13-02 Stop Event
for further descrip-
tions of options and their functions.
Table 231: Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
AU363928304090en-000101 / 130R0982
126 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide