0-37 Display Text 1
Default value: N/A
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: VisibleString
Change during operation: True
Use this parameter to write an individual text string to be read via serial communication. Device ID can be included. Only used when
running BACnet.
Table 26: Range:
Min: 0
Max: 0
Default value: N/A
0-38 Display Text 2
Default value: N/A
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: VisibleString
Change during operation: True
Use this parameter to write an individual text string to be read via serial communication. Only used when running BACnet.
Table 27: Range:
Min: 0
Max: 0
Default value: N/A
0-39 Display Text 3
Default value: N/A
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: VisibleString
Change during operation: True
Use this parameter to write an individual text string to be read via serial communication. Only used when running BACnet.
Table 28: Range:
Min: 0
Max: 0
Default value: N/A
4.2.4 0-4* LCP Keypad
Enable, disable, and password protect individual keys on the LCP.
0-40 [Hand on] Key on LCP
Default value: [1] Enabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Table 29: Option:
[0]
Disabled
To avoid unintended start of the drive in hand-on mode, select
[0] Disabled
.
[1]
Enabled
[Hand On] is enabled.
0-42 [Auto on] Key on LCP
Default value: [1] Enabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Table 30: Option:
[0]
Disabled
To avoid unintended start of the drive, select
[0] Disabled
.
[1]
Enabled
[Auto On] is enabled.
AU363928304090en-000101 / 130R0982
38 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide