Table 198: Option:
[0]
Digital input
Activate DC brake via a digital input.
[1]
Bus
Activate DC brake via the serial communication port.
[2]
Logic AND
Activate DC brake via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate DC brake via the serial communication port or via 1 of the digital inputs.
8-53 Start Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the drive start function via the terminals (digital input) and/or via the bus.
Table 199: Option:
[0]
Digital input
Activate a start command via a digital input.
[1]
Bus
Activate a start command via the serial communication port.
[2]
Logic AND
Activate a start command via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate a start command via the serial communication port or via 1 of the digital inputs.
8-54 Reversing Select
Default value: [0] Digital input
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the drive reverse function via the terminals (digital input) and/or via the bus.
Table 200: Option:
[0] Digital input
Activate a reverse command via a digital input.
[1] Bus
Activate a reverse command via the serial communication port.
[2] Logic AND
Activate a reverse command via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3] Logic OR
Activate a reverse command via the serial communication port or via 1 of the digital inputs.
8-55 Set-up Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the drive setup selection via the terminals (digital input) and/or via the bus.