Table 201: Option:
[0]
Digital input
Activate the setup selection via a digital input.
[1]
Bus
Activate the setup selection via the serial communication port.
[2]
Logic AND
Activate the setup selection via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate the setup selection via the serial communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when
parameter 8-01 Control Site
is set to
[0] Digital and control word
.
Select control of the drive preset reference selection via the terminals (digital input) and/or via the bus.
Table 202: Option:
[0] Digital input Activate the preset reference selection via a digital input.
[1] Bus
Activate the preset reference selection via the serial communication port.
[2] Logic AND
Activate the preset reference selection via the fieldbus/serial communication port, and via 1 of the digital
inputs.
[3] Logic OR
Activate the preset reference selection via the serial communication port or via 1 of the digital inputs.
4.9.5 8-7* BACnet
8-70 BACnet Device Instance
Default value: 1
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
Enter a unique ID number for the BACnet device.
Table 203: Range:
Min: 0
Max: 4194303
Default value: 1
8-72 MS/TP Max Masters
Default value: 127
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int8
Change during operation: True
Define the address of the master, which holds the highest address in this network. Decreasing this value optimizes polling for the
token.
Table 204: Range:
Min: 0
Max: 127
Default value: 127
8-73 MS/TP Max Info Frames
Default value: 1
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int16
Change during operation: True