Setpoint 1 is used in closed loop as the reference to compare the feedback values with. The setpoint can be offset with digital,
analog, or bus references.
Table 365: Range:
Min: -4999.000
Max: 4999.000 ProcessCtrlUnit
Default value: 0 ProcessCtrlUnit
4.15.3 20-6* Sensorless
Parameters for sensorless. See also
parameter 16-26 Power Filtered [kW]
,
parameter 16-27 Power Filtered [hp]
,
parameter 18-50 Sensor-
less Readout [unit]
, and
parameter 20-00 Feedback 1 Source
.
20-60 Sensorless Unit
Default value: [20] l/s
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the unit to be used with
parameter 18-50 Sensorless Readout [unit]
.
Table 366: Option:
[0]
None
[20]
l/s
[23]
m
3
/s
[24]
m
3
/min
[25]
m
3
/h
[71]
bar
[73]
kPa
[74]
m Wg
[75]
mm Hg
[120]
GPM
[121]
gal/s
[122]
gal/min
[123]
gal/h
[124]
CFM
[125]
ft
3
/s
[126]
ft
3
/min
[170]
psi
[171]
lb/in
2
[172]
in WG
[173]
ft WG
[174]
in Hg
AU363928304090en-000101 / 130R0982 | 161
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide