The jog speed is a fixed output speed at which the drive runs when the jog function is activated. See also
parameter 3-80 Jog Ramp
Time
.
Table 100: Range:
Min: 0 Hz
Max: 500.0 Hz
Default value: 5 Hz
3-14 Preset Relative Reference
Default value: 0%
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: int16
Change during operation: True
Define the fixed value in % to be added to the variable value defined in
parameter 3-18 Relative Scaling Reference Resource
.
The sum of fixed and variable values (labeled Y in the following illustration) is multiplied by actual reference (labeled X in the follow-
ing illustration). This product is added to actual reference:
X
+
X
×
Y
100
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
e3
0b
a0
59
.1
3
Z
Illustration 10: Preset Relative Reference
Table 101: Range:
Min: -100%
Max: 100%
Default value: 0%
3-15 Reference 1 Source
Default value: [1] Analog Input 53
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the input to be used for the 1
st
reference signal.
Parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
, and
parameter 3-17 Reference 3 Source
define up to 3 different reference signals. The sum of these reference signals defines the actual
reference.
Table 102: Option:
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Pulse input 29
[11]
Local bus reference
3-16 Reference 2 Source
Default value: [2] Analog Input 54
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the input to be used for the 2
nd
reference signal.
Parameter 3-15 Reference 1 Source
,
parameter 3-16 Reference 2 Source
, and
parameter 3-17 Reference 3 Source
define up to 3 different reference signals. The sum of these reference signals defines the actual
reference.