Table 183: Option:
[0]
Digital and ctrl.word
Control by using both digital input and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword only
Control by using control word only.
8-02 Control Source
Default value: [1] None
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the source of the control word.
Table 184: Option:
[0]
None
[1]
FC Port
8-03 Control Timeout Time
Default value: Configuration dependent
Parameter type: Range
2-setup: 1 setup
Conversion index: -1
Data type: u_int16
Change during operation: True
Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates
that the serial communication has stopped. The function selected in
parameter 8-04 Control Timeout Function
is carried out.
Table 185: Range:
Min: 0.1 s
Max: 6500 s
Default value: Configuration dependent
8-04 Control Timeout Function
Default value: [0] Off
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select the timeout function. The timeout function is activated when the control word fails to be updated within the time period
specified in
parameter 8-03 Control Timeout Time
.
Table 186: Option:
[0]
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[6]
Qstop and trip
[20]
N2 override release
[26]
Trip
AU363928304090en-000101 / 130R0982
104 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide