14-28 Production Settings
Default value: [0] No action
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Service use only.
Table 247: Option:
[0]
No action
[1]
Service reset
[3]
Software Reset
14-29 Service Code
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
Service use only.
Table 248: Range:
Min: 0
Max: 2147483647
Default value: 0
4.11.4 14-3* Current Limit Ctrl.
Parameters for configuring the current limit controller, which is activated when the motor current exceeds the preset current limits
(see
parameter 4-18 Current Limit
). These parameters are used to reduce torque as quickly as possible without losing control of the
motor.
14-30 Current Lim Ctrl, Proportional Gain
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: 0
Data type: u_int16
Change during operation: True
Enter the proportional gain value for the current limit controller. A higher value makes the controller react faster. Excessive value
setting leads to controller instability.
Table 249: Range:
Min: 0%
Max: 500%
Default value: 100%
14-31 Current Lim Ctrl, Integration Time
Default value: 0.020 s
Parameter type: Range
2-setup: All setups
Conversion index: -3
Data type: u_int16
Change during operation: True
Control the current limit control integration time. Setting it to a lower value makes it react faster. A setting too low leads to control
instability.
Table 250: Range:
Min: 0.002 s
Max: 2 s
Default value: 0.020 s
14-32 Current Lim Ctrl, Filter Time
Default value: 26.0 ms
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True