[168] Drive in hand mode
The output is high when the drive is in hand-on mode (as indicated by the LED light above
[Hand On]).
[169] Drive in auto mode
The output is high when the drive is in auto-on mode (as indicated by the LED light above [Auto
On]).
[188] AHF Capacitor Con-
nect
Connect or disconnect AHF capacitor.
[190] No-Flow
A no-flow condition has been detected. See
parameter group 22-2* No-Flow Detection
.
[191] Dry Pump
A dry-pump condition has been detected. Enable the function in
parameter 22-26 Dry Pump
Function
.
[192] End Of Curve
An end-of-curve condition has been detected. Enable the function in
parameter 22-50 End of
Curve Function
.
[193] Sleep Mode
The drive/system has entered sleep mode. See
parameter group 22-4* Sleep Mode
.
[194] Broken Belt Function
A broken-belt condition has been detected. Enable the function in
parameter 22-60 Broken Belt
Function
.
[196] Fire Mode
The drive is operating in fire mode. See
parameter group 24-0* Fire Mode
.
[198] Drive Bypass
To be used as a signal for activating an external electromechanical bypass, switching the motor
directly on line. See
parameter group 24-1* Drive Bypass
.
[200] Full capacity
The drive enters full capacity mode.
[201] Pump 1 running
Pump 1 is running.
[202] Pump 2 running
Pump 2 is running.
[203] Pump 3 running
Pump 3 is running.
[204] Pump 4 running
Pump 4 is running.
[205] Pump 5 running
Pump 5 is running.
[211] Cascade Pump 1
Cascade pump 1 is running.
[212] Cascade Pump 2
Cascade pump 2 is running.
[213] Cascade Pump 3
Cascade pump 3 is running.
[214] Cascade Pump 4
Cascade pump 4 is running.
[215] Cascade Pump 5
Cascade pump 5 is running.
5-34 On Delay, Digital Output
Default value: 0.01 s
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Enter the delay time before the digital output is switched on. The digital output (terminal 42/45) condition must not be interrupted
during the delay time.
Table 140: Range:
Min: 0 s
Max: 600 s
Default value: 0.01 s