13-00 SL Controller Mode
Default value: [0] Off
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To enable the smart logic control to start when a start command is present, for example, via a digital input, Select
[1] On
. To disable
the smart logic control, select
[0] Off
.
Table 218: Option:
[0]
Off
Disable the smart logic controller.
[1]
On
Enable the smart logic controller.
13-01 Start Event
Default value: [39] Start command
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
To activate smart logic control, select the boolean (True or False) input.
Table 219: Option:
[0]
False
Enter the fixed value False in the logic rule.
[1]
True
Enter the fixed value True in the logic rule.
[2]
Running
The motor runs.
[3]
In range
The motor runs within programmed current ranges (
parameter 4-50 Warning Current Low
and
pa-
rameter 4-51 Warning Current High
).
[4]
On reference
The motor runs at reference speed.
[7]
Out of current range The motor current is outside the range set in
parameter 4-18 Current Limit
.
[8]
Below I low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[9]
Above I high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[16] Thermal warning
The thermal warning turns on when the temperature exceeds the limit in the motor, the drive, or
the thermistor.
[17] Mains out of range
Mains phase loss warning or alarm, if
parameter 14-12 Function at Mains Imbalance
is not set at
[2]
Disabled
.
[18] Reversing
The drive reverses.
[19] Warning
A warning is present.
[20] Alarm (trip)
An alarm is present.
[21] Alarm (trip lock)
A trip lock alarm is present.
[22] Comparator 0
Use the result of comparator 0 in the logic rule.
[23] Comparator 1
Use the result of comparator 1 in the logic rule.
[24] Comparator 2
Use the result of comparator 2 in the logic rule.
[25] Comparator 3
Use the result of comparator 3 in the logic rule.
[26] Logic rule 0
Use the result of logic rule 0 in the logic rule.