16-73 Counter B
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: int16
Change during operation: True
View the present value of counter B. Counters are useful as comparator operands, see
parameter 13-10 Comparator Operand
. The
value can be reset or changed either via digital inputs (
parameter group 5-1* Digital Inputs
) or by using an SLC action (
parameter
13-52 SL Controller Action
).
Table 338: Range:
Min: -32768
Max: 32767
Default value: 0
16-79 Analog output 45 [mA]
Default value: 0 mA
Parameter type: Range
2-setup: 1 setup
Conversion index: -2
Data type: u_int16
Change during operation: True
View the actual value at output 45 in mA. The value shown reflects the selection in
parameter 6-70 Terminal 45 Mode
and
parameter
6-71 Terminal 45 Analog Output
.
Table 339: Range:
Min: 0 mA
Max: 20 mA
Default value: 0 mA
4.13.6 16-8* Fieldbus & FC Port
Parameters for reporting the bus references and control words.
16-86 FC Port REF 1
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: int16
Change during operation: True
View the last received reference from the FC port.
Table 340: Range:
Min: -32768
Max: 32767
Default value: 0
4.13.7 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
View the alarm word sent via the serial communication port in hex code.
Table 341: Range:
Min: 0
Max: 4294967295
Default value: 0
16-91 Alarm Word 2
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
View the alarm word 2 sent via the serial communication port in hex code.
Table 342: Range:
Min: 0
Max: 4294967295
Default value: 0
AU363928304090en-000101 / 130R0982
154 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide