Set the duration of the DC-brake current set in
parameter 2-01 DC Brake Current
, once activated.
Table 89: Range:
Min: 0 s
Max: 60 s
Default value: 10 s
2-04 DC Brake Cut In Speed
Default value: 0 Hz
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
This parameter is for setting the DC-brake cut-in speed at which
parameter 2-01 DC Brake Current
is to be active with a stop com-
mand.
Table 90: Range:
Min: 0 Hz
Max: 500 Hz
Default value: 0 Hz
2-06 Parking Current
Default value: 100%
Parameter type: Range
2-setup: All setups
Conversion index: -
Data type: u_int16
Change during operation: True
Set current as percentage of rated motor current,
parameter 1-24 Motor Current
. Active with
parameter 1-73 Flying Start
. The parking
current is active during the time period set in
parameter 2-07 Parking Time
.
N O T I C E
Parameter 2-06 Parking Current
is only active when 1 of the PM motor construction options is selected in
parameter 1-10 Motor
Construction
.
Table 91: Range:
Min: 0%
Max: 150%
Default value: 100%
2-07 Parking Time
Default value: 3 s
Parameter type: Range
2-setup: All setups
Conversion index: -1
Data type: u_int16
Change during operation: True
Set the duration of the parking current time set in
parameter 2-06 Parking Current
. Active with
parameter 1-73 Flying Start
.
N O T I C E
Parameter 2-07 Parking Time
is only active when options of
parameter 1-10 Motor Construction
are set to enable PM motors.
Table 92: Range:
Min: 0.1 s
Max: 60 s
Default value: 3 s
4.4.2 2-1* Brake Energy Function
Parameter group for selecting dynamic brake parameters.
2-10 Brake Function
Default value: [0] Off
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
AU363928304090en-000101 / 130R0982
58 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide