[213] Cascade Pump 3
Cascade pump 3 is running.
[214] Cascade Pump 4
Cascade pump 4 is running.
[215] Cascade Pump 5
Cascade pump 5 is running.
5-41 On Delay, Relay
Default value: 0.01 s
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Enter the delay of the relay cut-in time. Select 1 of 2 internal mechanical relays in an array function. See
parameter 5-40 Function
Relay
for details.
Selected
event
Relay
output
Selected
event
Relay
output
On delay
P 5-41
On delay
P 5-41
Off delay
P 5-42
e3
0b
a1
71
.1
1
Illustration 12: On Delay, Relay
If the selected event condition changes before the on delay timer expires, the relay output is unaffected.
Table 143: Range:
Min: 0 s
Max: 600 s
Default value: 0.01 s
5-42 Off Delay, Relay
Default value: 0.01 s
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Enter the delay of the relay cutout time. Select 1 of 2 internal mechanical relays in an array function. See
parameter 5-40 Function
Relay
for details. If the selected event condition changes before a delay timer expires, the relay output is unaffected.
Selected
event
Relay
output
On delay
P 5-41
Off delay
P 5-42
e3
0b
a1
72
.1
1
Illustration 13: Off Delay, Relay
If the selected event condition changes before the off delay timer expires, the relay output is unaffected.
AU363928304090en-000101 / 130R0982 | 89
Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide