4.9.2 8-3* FC Port Settings
8-30 Protocol
Default value: [0] FC
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select the protocol for the integrated RS485 port.
Table 187: Option:
[0]
FC
Communication according to the FC Protocol.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol.
[3]
Metasys N2
Communication protocol. The N2 software protocol is designed to be general in nature to accommo-
date the unique properties each device may have.
[4]
FLN
Communication according to the FLN protocol.
[5]
BACnet
Communication according to the BACNet protocol.
[20] LEN
Communication according to the LEN protocol.
[24] Vertiv MB Con-
verter
Communication according to the Vertiv MB Converter protocol.
8-31 Address
Default value: Configuration dependent
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Enter the address for the RS485 port. Valid range: 1–126 for FC-bus OR 1– 247 for Modbus.
Table 188: Range:
Min: 0.0
Max: 247
Default value: Configuration dependent
8-32 Baud Rate
Default value: -
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select the baud rate for the RS485 port. Default value refers to the FC protocol. Changing the protocol in
parameter 8-30 Protocol
may change the baud rate.
Table 189: Option:
[0]
2400 Baud
–
[1]
4800 Baud
Default setting for FLN.
[2]
9600 Baud
Default setting for:
BACnet.
Metasys N2.
[3]
19200 Baud
Default setting for Modbus RTU.
[4]
38400 Baud
–