[3]
Drive ready/remote
control
The drive is ready for operation in auto-on mode.
[4]
Standby/no warning
The drive is ready for operation. No start or stop command is given. No warnings are present.
[5]
Drive running
The motor runs.
[6]
Running/no warning
The motor runs, and no warnings are present.
[7]
Run in range/no warn-
ing
The motor runs within the programmed current ranges, see
parameter 4-50 Warning Current
Low
and
parameter 4-51 Warning Current High
. No warnings are present.
[8]
Run on ref/no warning
The motor runs at reference speed and with no warnings.
[9]
Alarm
An alarm activates output.
[10]
Alarm or warning
An alarm or warning activates output.
[12]
Out of current range
The motor current is outside the ranges set in
parameter 4-50 Warning Current Low
and
parame-
ter 4-51 Warning Current High
.
[13]
Below current, low
The motor current is lower than the limit set in
parameter 4-50 Warning Current Low
.
[14]
Above current, high
The motor current is higher than the limit set in
parameter 4-51 Warning Current High
.
[16]
Below speed, low
The drive output speed is lower than the limit set in
parameter 4-40 Warning Freq. Low
.
[17]
Above speed, high
The drive output speed is higher than the limit set in
parameter 4-41 Warning Freq. High
.
[19]
Below feedback, low
The feedback is lower than the limit set in
parameter 4-56 Warning Feedback Low
.
[20]
Above feedback, high
The feedback is higher than the limit set in
parameter 4-57 Warning Feedback High
.
[21]
Thermal warning
The thermal warning turns on when the temperature exceeds the limit in motor, drive, or ther-
mistor.
[22]
Ready, no thermal
warning
The drive is ready for operation and no thermal warning is present.
[23]
Remote, ready, no
thermal warning
The drive is ready for operation in auto mode, and no thermal warning is present.
[24]
Ready, Voltage OK
The drive is ready for operation and mains voltage is within the specified voltage range.
[25]
Reverse
The motor runs/is ready to run clockwise when logic = 0 and counterclockwise when logic = 1.
Output changes as soon as reversing signal is applied.
[26]
Bus OK
Active communication (no timeout) via serial communication port.
[35]
External Interlock
See
[7] External Interlock
in the
parameter group 5-1* Digital Input
.
[36]
Control word bit 11
Bit 11 in control word controls the relay.
[37]
Control word bit 12
Bit 12 in control word controls the relay.
[41]
Below reference, low
The reference is lower than the limit set in
parameter 4-54 Warning Reference Low
.
[42]
Above ref, high
The reference is higher than the limit set in
parameter 4-55 Warning Reference High
.
[45]
Bus Control
The output is configured in
parameter 5-90 Digital & Relay Bus Control
.
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If comparator 0 is evaluated as true, the output goes
high. Otherwise, it is low.