Parameter 1-10 Motor Construction
[0] Asynchron
[1] PM, non salient SPM
[3] PM, salient IPM
Parameter 2-07 Parking Time
x
x
Parameter 2-10 Brake Function
x
x
x
Parameter 2-16 AC brake Max. Current
x
Parameter 2-17 Over-voltage Control
x
x
x
Parameter 4-10 Motor Speed Direction
x
x
x
Parameter 4-14 Motor Speed High Limit [Hz]
x
x
x
Parameter 4-18 Current Limit
x
x
x
Parameter 4-19 Max Output Frequency
x
x
x
Parameter 4-58 Missing Motor Phase Function
x
x
x
Parameter 14-01 Switching Frequency
x
x
x
Parameter 14-03 Overmodulation
x
x
x
Parameter 14-07 Dead Time Compensation Level
x
x
x
Parameter 14-08 Damping Gain Factor
x
x
x
Parameter 14-09 Dead Time Bias Current Level
x
x
x
Parameter 14-10 Mains Failure
x
x
x
Parameter 14-11 Mains Fault Voltage Level
x
x
x
Parameter 14-12 Function at Mains Imbalance
x
x
x
Parameter 14-27 Action At Inverter Fault
x
x
x
Parameter 14-40 VT Level
x
x
x
Parameter 14-41 AEO Minimum Magnetisation
x
x
x
Parameter 14-44 d-axis current optimization for IPM
x
Parameter 14-50 RFI Filter
x
Parameter 14-51 DC-Link Voltage Compensation
x
x
x
Parameter 14-55 Output Filter
x
x
x
Parameter 14-64 Dead Time Compensation Zero Current Level
x
x
x
Parameter 14-65 Speed Derate Dead Time Compensation
x
x
x
Parameter 30-22 Locked Rotor Protection
x
x
Parameter 30-23 Locked Rotor Detection Time [s]
x
x
1-14 to 1-17 VVC
+
PM
The default control parameters for VVC+ PM motor control core are optimized for applications and inertia load in the range of
50>Jl/Jm>5. Jl is load inertia from the application and Jm is machine inertia.
For low inertia applications (Jl/Jm<5), it is recommended that
parameter 1-17 Voltage filter time const.
is increased with a factor of 5–
10. Sometimes,
parameter 14-08 Damping Gain Factor
should also be reduced to improve performance and stability.
For high-inertia applications (Jl/Jm>50), increase
parameter 1-15 Low Speed Filter Time Const.
and
parameter 1-16 High Speed Filter
Time Const.
to improve performance and stability.